Trane 5YCZ5060A1115A, Priority, 5T, 15.2 SEER2, Two Stage Gas Furnace / Air Conditioner Package Unit

Trane 5YCZ5060A1115A, Priority, 5T, 15.2 SEER2, Two Stage Gas Furnace / Air Conditioner Package Unit

Manufacturer: Trane International Inc
Brand: TRANE®
Part #: 390638
MPN: 5YCZ5060A1115A
Customer Part #:
Min. Order Qty: 1
Login for Availability
Login for Price
AFUE Rating      :      81 %
AFUE      :      81%
Additional Information      :      Outdoor Fan - HP: 1/4|Outdoor Fan - Number of Speeds: 1|Outdoor Fan - Speed: 825|Outdoor Fan - Type: Propeller|Outdoor Unit: Fan Motor FLA: 1.7|Power Input kW: 5.12/2.86 (High/Low)|Power Supply: 208/230 V/1 Phase/60 Hz|Refrigerant Charge lbs: 9 lbs - 12.8 oz|Refrigerant Type: R-454B|SEER2: 15.2|Sound Rating (dB): 73|Subcooling Temperature: 9 deg F|Temperature Rise (Min-Max) deg F: 30 to 60
Airflow CFM      :      1780/1270 (High/Low)
CFM Rating      :      2,000 cfm
Capacity (BtuH)      :      46000 (Low)
Combustion Fan Drive      :      Direct
Combustion Fan Motor HP      :      1/20
Combustion Fan Power      :      208/230 V/1 Phase/60 Hz
Combustion Fan Speeds      :      2
Combustion Fan Type      :      Centrifugal
Combustion Fan-RPM      :      3350/2600
Compressor LRA      :      147.3
Compressor Power Rating      :      208/230 V/1 Phase/60 Hz
Compressor RLA      :      25.2
Compressor Type      :      Scroll
Cooling Capacity (BtuH)      :      60000
Cooling Capacity      :      60,000 BTU
Crated Dimensions (H X W X D)      :      52 x 47 x 62 in
Decibel Rating      :      73 dBA
Drill Size Nat Gas (Qty - Drill Size)      :      3 - #32
EER2      :      11.5
Filter Furnished      :      No
Filter Type Recommended      :      Throwaway
Filter-Face Area sq-ft      :      5.3
Frequency Rating      :      60 Hz
Fuse Rating      :      60 A
Heating Capacity Stage 1      :      92000
Heating Capacity Stage 2      :      115000
Heating Capacity      :      115,000 BTU
Indoor Coil-Drain Connection Size      :      3/4 in NPT
Indoor Coil-FPI      :      15
Indoor Coil-Face Area sq-ft      :      5
Indoor Coil-Refrigeration Control      :      TXV
Indoor Coil-Rows      :      4
Indoor Coil-Type      :      Plate Fin
Indoor Coil: Tube Size (In.)      :      0.375
Indoor Fan Type      :      ECM
Indoor Fan-Dia x W in      :      11.87 x 10.68
Indoor Fan-Drive      :      Direct
Indoor Fan-Number of Speeds      :      Variable
Indoor Fan: Motor HP (Standard/Oversized)      :      1
Indoor Unit: Fan Motor FLA      :      6.9
Indoor Unit: Fan Motor Speed RPM      :      Variable
Input BTU Rating      :      60,000 Btu/hr
Line Size - Suction (In)      :      1/2
MCA      :      40
Max Fuse      :      60 A
Model      :      5YCZ5
Number of Stages      :      Two
Outdoor Coil-FPI      :      24
Outdoor Coil-Face Area sq-ft      :      23.57
Outdoor Coil-Rows      :      2
Outdoor Coil-Tube Size (In)      :      3/8
Outdoor Coil-Type      :      Spine Fin
Outdoor Coil: Refrigerant Control      :      Expansion Valve
Outdoor Fan - CFM      :      4700
Outdoor Fan - Diameter In      :      28.2
Outdoor Fan - Drive      :      Direct
Phase      :      1 ph
Refrigerant Type      :      R-454B
SEER 2 Rating      :      15.2
Series      :      Priority
Tonnage      :      5.0 ton
Voltage Rating      :      208/230 V

Trane 5YCZ5060A1115A, Priority, 5T, 15.2 SEER2, 60,000 BTU Cooling, 115,000 BTU Heating, 81% AFUE, R454B, TXV Metering, ECM Motor, Two Stage Gas Furnace / Air Conditioner Package Unit

  • The Climatuff® two-stage compressor features internal over temperature and pressure protector, total dipped hermetic motor. Other features include: centrifugal oil pump, and low vibration and noise.
  • Indoor Air Fan — Direct-drive, forward-curved, centrifugal wheel in a Composite Vortica® Blower housing.
  • The Spine Fin ™ condenser coil shall be continuously wrapped, corrosion resistant all aluminum with minimum brazed joints. The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is
  • protected on all four sides by louvered panels.
  • Gas-Fired Heating System — Models shall provide completely assembled, wired and piped gas fired heating systems within unit.
  • Forced Combustion Blower — Insures flame stability under varying wind conditions. Gives higher combustion efficiency and location flexibility.
  • Heat Exchanger — stainless steel tubes. Free floating design.
  • Lower global warming potential R-454B refrigerant
  • Burners — stainless steel. Multi-port inshot.

back To Top