Water Furnace Aston 101K049BL114C00A0 Geothermal Heat Pump, 4 Tons, R-410A, Vertical, Downflow, Left Return, 208/230 V, 17.2 EER (WLHP), 24.5 EER (GWHP), 19.3 EER (GLHP), 1" Swivel FPT (Water), 3/4" PVC Socket (Condensate), Knockout (Electrical) Connection, 1-Phase
Water Furnace Aston 101K049BL114C00A0 Geothermal Heat Pump, 4 Tons, R-410A, Vertical, Downflow, Left Return, 208/230 V, 17.2 EER (WLHP), 24.5 EER (GWHP), 19.3 EER (GLHP), 1" Swivel FPT (Water), 3/4" PVC Socket (Condensate), Knockout (Electrical) Connection, 1-Phase
| Amperage Rating | : | 34.5 A (FLA), 39.8 A (MCA) |
| BTU Rating | : | 49,100 BTU/hr (Cooling, WLHP); 54,100 BTU/hr (Cooling, GWHP); 50,800 BTU/hr (Cooling, GLHP); 59,000 BTU/hr (Heating, WLHP); 47,200 BTU/hr (Heating, GWHP); 38,200 BTU/hr (Heating, GLHP) |
| Blower Size | : | 11" Diam x 10" W |
| CFM Rating | : | 1,600 CFM |
| Coil Rating | : | 4 Tons |
| Color | : | Off White |
| Compressor Type | : | Dual Capacity Scroll |
| Configuration | : | Vertical, Downflow, Left Return |
| Connection Type | : | 1" Swivel FPT (Water), 3/4" PVC Socket (Condensate), Knockout (Electrical) |
| Dimensions | : | 62-1/2" H x 25-1/2" W x 31-1/2" D |
| Drive Type | : | Direct Drive |
| EER Rating | : | 17.2 EER (WLHP), 24.5 EER (GWHP), 19.3 EER (GLHP) |
| Filter Size | : | 32" x 30" x 2" |
| Finish | : | Powder Coated (1,000 Hour Salt Spray Rated) |
| Flow Rate | : | 12 GPM |
| Frequency Rating | : | 60 Hz |
| Fuse Rating | : | 60 A |
| HP Rating | : | 1 HP (Blower Motor) |
| Material | : | Galvanized Steel (Cabinet), Aluminum/Copper (Air Coil Tubes), Aluminum (Air Coil Fins), Cupro-Nickel/Steel (Coaxial Heat Exchanger) |
| Model | : | 101K049BL114C00A0 |
| Mounting Type | : | Vertical Downflow |
| Number of Stages | : | 2 |
| Phase | : | 1 |
| Pressure Rating | : | 614.7 PSI (Refrigerant), 464.7 PSI (Water) |
| Refrigerant Type | : | R-410A |
| Series | : | Aston |
| Temperature Rating | : | 20-120 °F (Entering Water) |
| Tonnage | : | 4 tons |
| Voltage Rating | : | 208/230 V |
The Aston Series Geothermal Heat Pump provides efficient heating and cooling in a vertical downflow package unit configuration. This 4-ton, dual-capacity system utilizes environmentally friendly R-410A refrigerant and achieves high EER ratings across various operating conditions (Water Loop, Ground Water, Ground Loop). It features a robust Copeland UltraTechâ„¢ dual capacity scroll compressor for reliable performance.Constructed with a heavy-gauge galvanized steel cabinet finished with a durable, corrosion-resistant powder coating for longevity. The unit incorporates a high-efficiency cupronickel coaxial heat exchanger with ThermaShield insulation and a large air coil designed for optimal moisture removal. An energy-efficient 1 HP ECM blower motor ensures consistent airflow.
Water Furnace Geothermal Heat Pump, Model: Aston, 4 Tons, R-410A, Vertical, Downflow, Left Return, 208/230 V, 17.2 EER (WLHP), 24.5 EER (GWHP), 19.3 EER (GLHP), 1" Swivel FPT (Water), 3/4" PVC Socket (Condensate), Knockout (Electrical) Connection, 1-Phase, 62-1/2" H x 25-1/2" W x 31-1/2" D Dimensions, 1,600 CFM, 12 GPM, Direct Drive, Dual Capacity Scroll, 11" Diam x 10" W Blower Size, 1 HP (Blower Motor), Galvanized Steel (Cabinet), Aluminum/Copper (Air Coil Tubes), Aluminum (Air Coil Fins), Cupro-Nickel/Steel (Coaxial Heat Exchanger), Vertical Downflow, 32" x 30" x 2" Filter Size, 2 Stage, 49,100 BTU/hr (Cooling, WLHP); 54,100 BTU/hr (Cooling, GWHP); 50,800 BTU/hr (Cooling, GLHP); 59,000 BTU/hr (Heating, WLHP); 47,200 BTU/hr (Heating, GWHP); 38,200 BTU/hr (Heating, GLHP), 34.5 A (FLA), 39.8 A (MCA), 614.7 PSI (Refrigerant), 464.7 PSI (Water), 20-120 °F (Entering Water), 60 Hz, 60 A Fuse Rating, Off White
- Delivers efficient heating and cooling with dual-capacity scroll compressor technology.
- Achieves high energy efficiency with EER ratings up to 33.0 (Part Load, GWHP).
- Features a durable heavy-gauge galvanized steel cabinet with a corrosion-resistant powder coat finish.
- Incorporates a high-efficiency cupronickel coaxial heat exchanger with ThermaShield insulation.
- Equipped with an energy-saving 1 HP ECM blower motor for optimized airflow.
- Utilizes environmentally preferred R-410A refrigerant.
- Includes a standard 2-inch MERV 11 filter rack (32" x 30").